Office Alarm Connections - Alcatel-Lucent 1665 Installation Manual

Data multiplexer extend (dmxtend)
Hide thumbs Also See for 1665:
Table of Contents

Advertisement

Stand-alone installation testing
............................................................................................................................................................................................................................................................
Table 6-1 Office alarm connections
Conn.
J13-J14
Steps
........................................................................................................................................................................................................................
1
Connect the office alarm cable to J13 (ALM) on the backplane of the Alcatel-Lucent 1665
DMXtend shelf. If the shelf to be tested is part of a multiple shelf bay arrangement, the
office alarm cable connects to shelf 1.
........................................................................................................................................................................................................................
2
Verify that one of the function groups is equipped with any of the following circuit packs.
............................................................................................................................................................................................................................................................
6 - 4 2
Pin#
Color
1
BL-W
2
W-BL
3
O-W
4
W-O
5
G-W
6
W-G
7
BR-W
8
W-BR
9
S-W
10
W-S
11
BL-R
12
R-BL
LNW7 (28DS1)
LNW8 (56DS1E1)
LNW16 (12DS3/EC1)
LNW18 (12TMUX)
LNW19B (48DS3/EC1)
LNW20 (48TMUXDS3EC1)
LNW39/LNW391 (DS1/DS3/16/3)
LNW111 (3 DS3)
LNW112 (16/3 DS1/DS3)
LNW801 (56 DS1E1)
Designation
Name
RYMJV1
Minor Alarm Visible
RYMJV2
Minor Alarm Visible Return
RYMJA1
Minor Alarm Audible
RYMJA2
Minor Alarm Audible Return
RYMNV1
Major Alarm Visible
RYMNV2
Major Alarm Visible Return
RYMNA1
Major Alarm Audible
RYMNA2
Major Alarm Audible Return
RYCRV1
Critical Alarm Visible
RYCRV2
Critical Alarm Visible Return
RYCRA1
Critical Alarm Audible
RYCRA2
Critical Alarm Audible Return
Alcatel-Lucent 1665 DMXtend R10.0
365-372-327R10.0 Issue 1
January 2013