The following figure shows 2 examples on how the ground and the signal cable
screens can be connected:
xx1200000960
Example 1:
Example 2:
Product manual - IRC5 Compact
3HAC047138-001 Revision: M
Control cabinet
Where a good ground is available on all units, the best shielding is obtained
by grounding all screens at both ends on all units.
If the cable is terminated where a good ground is not available a noise
suppression capacitor can be used. The screens of the 2 cables must be
connected as shown in the figure, but not connected to the chassis of the
unit.
© Copyright 2009-2020 ABB. All rights reserved.
2 Installation and commissioning
2.6.2 Connecting cables to the controller
External unit
Example 1
Example 2
Continues on next page
Continued