WIRING (continued)
Wiring as a P Channel or N Channel output: The Switch Tek™ can be substituted for either a P Channel (PNP,
sourcing) output or an N Channel (NPN, sinking) output.
Normally Open DC Load as a P Channel Output:
The Red wire connects to Positive (+) of the power
supply and the Black wire connects to Negative ( ).
The Green wire is jumped to the Red wire while the
White wire is connected to the LOAD. Jumper the
LOAD to the Negative ( ) to complete the circuit.
Sensor Power
[RED & BLK wires] / 36 VDC Max.
5 ±1mA Dry / 22 ±1mA Wet
Normally Open DC Load as a N Channel Output:
The Red wire connects to Positive (+) of the power
supply and the Black wire connects to Negative ( ).
The White wire is jumped to the Black wire while the
Green wire is connected to the LOAD. Jumper the
LOAD to the Positive (+) to complete the circuit.
Sensor Power
[RED & BLK wires] / 36 VDC Max.
5 ±1mA Dry / 22 ±1mA Wet
Rev A
Normally Closed DC Load as a P Channel Output:
The Black wire connects to Positive (+) of the power
supply and the Red wire connects to Negative ( ). The
Green wire is jumped to the Black wire while the
White wire is connected to the LOAD. Jumper the
LOAD to the Negative ( ) to complete the circuit.
Relay Rating
[GRN & WHT wires] / 60 VA
Normally Closed DC Load as a N Channel Output:
The Black wire connects to Positive (+) of the power
supply and the Red wire connects to Negative ( ). The
White wire is jumped to the Red wire while the White
wire is connected to the LOAD. Jumper the LOAD to
the Positive (+) to complete the circuit.
Relay Rating
[GRN & WHT wires] / 60 VA