Inputs; Setpoints - ProMinent DULCOMETER PH-501 Assembly And Operating Instructions Manual

Compact controller
Table of Contents

Advertisement

5.10.2 Inputs

Tag
Description
LSHH-601
Level Switch High High
LSH-601
Level Switch High
LSHH-602
Level Switch High High
LSH-602
Level Switch High
PSL-601
Pressure Switch Low
PSL-602
Pressure Switch Low
VT-701
Vacuum Transmitter
VT-702
Vacuum Transmitter
VFD-701
VFD Status
VFD-702
VFD Status
FIT-701
Flow Indicating Transmitter
FQI-701
Flow Totalizer
FIT-702
Flow Indicating Transmitter
FQI-702
Flow Totalizer
LSH-801
Level Switch High
LSL-801
Level Switch Low Low

5.10.3 Setpoints

Tag
Description
MBR-1 Vac Mode
VT-701-SP
Permeate Setpoint
MBR-1 Vac Mode
VT-701-
Permeate High Flux
HFSP
Setpoint
VTAH-701-
MBR-1 Vacuum
SP
Transmitter Alarm High
MBR-2 Vac Mode
VT-702-SP
Permeate Setpoint
MBR-2 Vac Mode
VT-702-
Permeate High Flux
HFSP
Setpoint
newterra O&M Manual
© 2017 by newterra, ltd.
All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without prior written permission of newterra ltd.
HMI Display
Input Type
Units
Discrete N.C.
Discrete N.O.
Discrete N.C.
Discrete N.O.
Discrete N.C.
Discrete N.C.
Analog
Bar
Analog
Bar
Communcation
Communcation
Analog
GPM
Discrete N.O.
Pulse/Gal
Analog
GPM
Discrete N.O.
Pulse/Gal
Discrete N.C.
Discrete N.O.
Factory
Setpoint Range
Setpoint
and Units
-0.1 bar
-0.2 - 0 bar
-0.15 bar
-0.2 - 0 bar
-0.3 bar
-0.3 - 0 bar
-0.1 bar
-0.2 - 0 bar
-0.15 bar
-0.2 - 0 bar
1291 California Avenue, Brockville, ON K6V 5W3
(800) 420-4056 / www.newterra.com
Device
Datalog
Trending
Range and
(Y)
(Y)
Units
9-85"WC
9-85"WC
-1.0 - 1.0
Y
Y
Bar
-1.0 - 1.0
Y
Y
Bar
0-300lpm
Y
Y
1liter /
Pulse
0-300lpm
Y
Y
1liter /
Pulse
Setpoint
Alarm
Change
setpoint
Control
(Y/N)
Open
Open
Open
Y
Open
Open
newterra ltd.
Notes
64