5.4 Kitchen Inlet Module (TNK-101/2/3) Module

A schematic of the Kitchen Inlet Module is located on the INLET HMI screen and shown below.

5.4.1 Function

The Waste Water Treatment Plant accepts waste water from the local kitchen which contains
kitchen oils and greases. These need to be removed prior to being fed into the fine screens.
This is done by using TNK-101/2/3 as grease traps. The kitchen waste water enters TNK-101,
the solid food particles sink to the bottom, while lighter grease and oil floats to the top. The
relatively grease-free water is then fed into TNK-102 where the process is repeated to further
separate the oils and greases from the waste water. The same applies to TNK-103. The waste
water is then fed to the fine screens.

5.4.2 Inputs

TAG
Description
FIT-101
Flow Indicating Transmitter
FQI-101
Flow Totalizer
LSHH-101
Level Switch High High
LSHH-102
Level Switch High High
LSHH-103
Level Switch High High
newterra O&M Manual
© 2017 by newterra, ltd.
All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without prior written permission of newterra ltd.
HMI
Input Type
Display
Range and
Units
Analog
GPM
Discrete
Pulse/Gal
N.O.
Discrete
N.C.
Discrete
N.C.
Discrete
N.C.
1291 California Avenue, Brockville, ON K6V 5W3
(800) 420-4056 / www.newterra.com
Device
Device
Datalog
Span/PLC
Units
Scale
0-760lpm
0-760lpm
1 liter/
Pulse
newterra ltd.
Trending
(Y)
(Y)
Y
Y
47