Logic; Alarms - ProMinent DULCOMETER PH-501 Assembly And Operating Instructions Manual

Compact controller
Table of Contents

Advertisement

5.9.4 Logic

Tag
Description
Post Anox Mix
P-553
Pump
Post Anox Mix
P-554
Pump
Micro C Dosing
P-6103
Pump
Aeration
P-551
Transfer Pump
Feed to MBR-1
Aeration
P-552
Transfer Pump
Feed to MBR-2

5.9.5 Alarms

None
newterra O&M Manual
© 2017 by newterra, ltd.
All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without prior written permission of newterra ltd.
Control Logic
Interactions
The pump will run as long
Pump will be
as LSLL-501 is Active
Runs Duty standby with p-
501 switching every 120
hours
Dosing Pump will be ON
when FIT-701 or FT-702
has reached a user
adjustable volume of
permeate via DOSE
setpoint.
The aeration pump will
feed MBR tank T-601. The
pump will be ON when
level transmitter LT-501 >
LTL-501-SP and LSLL-501
= Active and LSLL-502 =
Pump will be
Active and MBR-1 is
Enabled.
The aeration pump will be
cycle ON/OFF when LT-
501 < LTL-501-SP and be
OFF if LSLL-501 = InActive
OR LSLL-502 = InActive
The aeration pump will
feed MBR tank T-602. The
pump will be ON when
level transmitter LT-501 >
LTL-501-SP and LSLL-501
= Active and LSLL-502 =
Pump will be
Active and MBR-2 is
Enabled.
The aeration pump will
cycle ON/OFF when LT-
501 < LTL-501-SP and be
OFF if LSLL-501 = InActive
OR LSLL-502 = InActive
1291 California Avenue, Brockville, ON K6V 5W3
Alarm
Output
Type
LALL-501:
Discrete
OFF
Discrete
Discrete
LAHH-601:
OFF
Discrete
MBR-1
Disabled
LAHH-602:
Discrete
OFF
MBR-2
Disabled
newterra ltd.
(800) 420-4056 / www.newterra.com
Hour
HOA
Meter
Control
Y
HOA
Y
HOA
HOA
Y
HOA
Y
HOA
62

Advertisement

Table of Contents
loading

This manual is also suitable for:

986214

Table of Contents