7.4 Sludge Decanting (TNK-901)

In order to maintain an optimal concentration of mixed liquor suspended solids (MLSS) (typically
10 g/L), a portion of the mixed liquor is periodically wasted by pumping from the Aeration Tank
(TNK-501) to the sludge holding tank (TNK-901). Wasted sludge in the sludge holding tank is
thickened by decanting supernatant back to the screen tank. Thickened sludge accumulates in
the sludge holding tanks until it is eventually pumped out for disposal.
Excess sludge will be wasted by P-503 from the Aeration Tank (TNK-501) every 10 mins at
noon. See below.
Tag
Description
P503 WASTE
When P-503 will waste
HOUR
P503 WASTE
Time that P-503 wastes for
SP
In order to decant the water from the sludge, the air to TNK-901 diffuser must be turned off.
See valve location below.
After the sludge has settled, that the operator would open the appropriate valve on TNK-901 to
decent off the water.
newterra O&M Manual
© 2017 by newterra, ltd.
All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without prior written permission of newterra ltd.
Factory
Setpoint Range and
Setpoint
Units
12pm
0-23
10min
0-99
1291 California Avenue, Brockville, ON K6V 5W3
(800) 420-4056 / www.newterra.com
Diffuser Air Valve
Decanting Valve