5.6 Equalization Tank (TNK-301) Module
A schematic of the Equalization Tank (TNK-301) is located on the EQ & PRE-ANOXIC HMI
screen and shown below.
5.6.1 Function
The EQ Tank (TNK-301) buffers variability in the influent flow rate to maintain a consistent flow
rate through the membranes and to reduce concentration fluctuations of influent constituents
(i.e. BOD, TSS etc.) through the MBR treatment system. Wastewater entering the newterra
MBR will first have undergone pre-treatment by fine screens and grease traps (kitchen waste).
The waste water is then pumped to the Pre-Anox Tank.
5.6.2 Inputs
Tag
Description
Level Switch
LSHH-301
High High
Level
LT-301
Transmitter
Temperature
TT-301
Transmitter
Level Switch
LSLL-301
Low Low
Pressure Switch
PSL-301
Low
newterra O&M Manual
© 2017 by newterra, ltd.
All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without prior written permission of newterra ltd.
HMI
Input Type
Display
Range and
Units
Discrete
N.C.
Analog
%
0-10 ftWC
Analog
°C
Discrete
N.O.
Discrete
N.C.
1291 California Avenue, Brockville, ON K6V 5W3
Device
Device
Datalog
Span/PLC
Units
Scale
0-10 ftWC
0-100c
0-100c
9-85"WC
newterra ltd.
(800) 420-4056 / www.newterra.com
Trending
Notes
(Y)
(Y)
Y
Y
n
n
Added to System
Must be above
all immersion
heaters in Tank
51