Membrane Filtration Operational Conditions - ProMinent DULCOMETER PH-501 Assembly And Operating Instructions Manual

Compact controller
Table of Contents

Advertisement

6.2.1.1 Membrane Filtration Operational Conditions

Parameter
Diffuser Relaxation
Relax Time
Backwashing
In-situ Chemically Enhanced
Backwash (CEB)
TMP
newterra O&M Manual
© 2017 by newterra, ltd.
All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without prior written permission of newterra ltd.
Recommended
Value
Effluent filtration must be turned off,
10 minutes/day
blower shuts down for 10 mins/day
Filtration must be off and blower are
1 min/10 min
operating continuously
Built-in backwash mode during
48 cycles
relaxation mode
Requires 3 L to fully backwash one
MCXL cassette. Frequency of CEB may
500 ppm as
vary. Refer to Membrane Cleaning
NaOCl
Section 7.3 for cleaning procedure.
< 0.2 bar (2.9
Membranes to be cleaned once the
psi)
TMP exceeds 0.2 bar (2.9 psi)
1291 California Avenue, Brockville, ON K6V 5W3
(800) 420-4056 / www.newterra.com
Notes
newterra ltd.
82