Mbr Alarm Trouble Shooting - ProMinent DULCOMETER PH-501 Assembly And Operating Instructions Manual

Compact controller
Table of Contents

Advertisement

7.5.2 MBR Alarm Trouble Shooting

Alarm
Alarm Name
Location
CP
PLC ALM
PWR FAIL
CP
ALM
ESTOP
Panel
ALM
Clarifier
TALL-201
B-201/
Clarifier
B-202 Fail
SCREEN
DISCHARG
LAHH-401
E
SCREEN
P-401 or
PUMP
P-402 FAIL
newterra O&M Manual
© 2017 by newterra, ltd.
All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without prior written permission of newterra ltd.
Alarm
Beacon
Description
Status
SHUTDOW
N PLC
FLASH
Fault
WARNING
SOLID
, Power Fail
E-Stop
FLASH
Temperatur
e alarm low
FLASH
low
Blower
B-201/B-
202 has
FLASH
potentially
failed
High high
level alarm
in Screen
FLASH
Module
discharge
tank
P-401/P-
402 has
FLASH
potentially
failed
1291 California Avenue, Brockville, ON K6V 5W3
(800) 420-4056 / www.newterra.com
Troubleshooting
Recommendatio
n
Turn off entire
system. Wait 10
seconds before
restoring power.
Power has failed
to the unit
Check all
locations of E-
Stop Buttons to
ensure they are
not pushed in.
Check for
building heater
malfunction.
Assess influent
water temperature.
water temperature
Check blower for
failure. Check
breaker
Potential
discharge tank
pump
P-401/P-402
failure Check
Breaker
P-401/P-402 for
failure. Check
Breaker
newterra ltd.
Remedy Action
Please contact
newterra -PLC
problem
Press Reset
Pull out E-Stop
Replace heater.
Take action to
increase influent
Replace blower
B-201/B-202.
Replace pump
Replace pump
P-401/P-402
114

Advertisement

Table of Contents
loading

This manual is also suitable for:

986214