5.10.4 Logic

Tag
Description
MBR Tank
B-601
Blower
MBR Tank
B-602
Blower
Permeate
P-701
Transfer Pump
newterra O&M Manual
© 2017 by newterra, ltd.
All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without prior written permission of newterra ltd.
Control Logic
The membrane tank blower will be
ON when the System is in Run. And
the MBR 1 is enabled
The membrane tank blower will be
ON when the System is in Run. And
the MBR 2 is enabled
The permeate pump will be ON when
MBR-1 is Enabled & level switch
LSH-601 = Active & LT-501 >
LT501-PERM-SP
The Pump will perform a
PULL/RELAX Cycle. The pump will
be ON for the duration specified by
the PERM-PULL-TIME setpoint and
then be OFF for the duration of the
RELAX-TIME setpoint. This will
generate one PULL/RELAX Cycle.
The VFD Speed of the pump will
operate based on the following:
In FLOW MODE:
The VFD Speed will operate based
on a PID loop to maintain the
flowrate setpoint FT-701-SP.
IF the vacuum transmitter VT-701 > -
0.25 bar then the pump will switch to
VAC MODE.
IF the level transmitter LT-301 >
FLUX-SP, the pump will run via PID
loop to maintain a high flow setpoint
FT-701-HFSP
In VAC MODE:
The VFD Speed will operate based
on a PID loop to maintain the
vacuum setpoint VT-701-SP.
IF the level transmitter LT-301 >
FLUX-SP, the pump will run via PID
loop to maintain a high flow setpoint
VT-701-HFSP
P-701 will be OFF if P-501 is OFF.
1291 California Avenue, Brockville, ON K6V 5W3
(800) 420-4056 / www.newterra.com
Alarm
Output
Interactions
Type
Discrete
MBR-1 Disabled
Discrete
MBR-2 Disabled
VFDA-701:
Communication
Pump Will be Off
newterra ltd.
Hour
Meter
Y
Y
Y
66