Alarms - ProMinent DULCOMETER PH-501 Assembly And Operating Instructions Manual

Compact controller
Table of Contents

Advertisement

5.8.5 Alarms

Alarm
Alarm Description
LAHH-501
Level Alarm High High
LAHH-502
Level Alarm High High
PHAH-501
pH Alarm High
PHAL-501
pH Alarm Low
Dissolved Oxygen Alarm
DOAL-501
Low
Dissolved Oxygen Alarm
DOALL-501
Low Low
TTAL-501
Low Temp TNK-501
PAL-501
Pressure Alarm Low
VFDA-501
VFD Fault
VFDA-502
VFD Fault
LALL-501
Low Low Level TNK-501
LALL-502
Low Low Level TNK-502
newterra O&M Manual
© 2017 by newterra, ltd.
All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without prior written permission of newterra ltd.
Actuation Control
LSHH-501 = Active
LSHH-501 = Active
pH-501 > PHAH-501-SP
pH-501 < PHAL-501-SP
DO-501 < DOAL-501-SP
DO-501 < DOAL-501-SP
TT-501<TTAL-501-SP
PSL-501 = InActive
LSLL-501 = OFF
LSLL-502 = OFF
1291 California Avenue, Brockville, ON K6V 5W3
(800) 420-4056 / www.newterra.com
Self
Delay
Resetting
(Y)
5s
Y
5s
Y
60s
60s
15m
4hrs
5s
Y
newterra ltd.
60