2) If backwash tank TNK-801 is full:
a. Disable membrane by holding down the disable membrane button for about 5
seconds
b. Turn SV-801 solenoid valves to off ("O")
c. Turn MV-701/702 (depending on the membranes to be cleaned) motorized valves
to hand ("H")
d. Turn pump P-801 to hand ("H") until the backwash tank has drained to the required
volume for chemical backwash (3L per cassette X 20 cassettes per module = 60
L OR approx. 1/4 capacity of TNK-801) – the exact volume can be determined by
backwash tank level drop. Note TNK-801 capacity is 272L.
e. Turn P-801 to off ("O")
7.3.1.2 Procedure – Organic Fouling Solution
Organic Fouling - NaOCl: 500 mg/L solution (acceptable range of 200 to 1000 mg/L). Used for
removal of organic fouling, which is the most common type of fouling in MBRs.
Volume of concentrated NaOCI required can be calculated with the following
formula,
V
m
V
x
C
: Volume of the solution (Gallon, or Litre), equal to 3 L multiplying the number of MCXL
cassettes 20 (60L per module);
: Concentrated NaOCI concentration (%)
: Volume of concentrated NaOCI required (Gallon, or Litre)
newterra O&M Manual
© 2017 by newterra, ltd.
All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without prior written permission of newterra ltd.
. 0
05
s
1291 California Avenue, Brockville, ON K6V 5W3
(800) 420-4056 / www.newterra.com
newterra ltd.