Hydrogen Peroxide; Conductivity [Ma]; Temperature [Ma], (As Main Measured Variable) - ProMinent DULCOMETER Assembly And Operating Instructions Manual

Multi-parameter controller dialog daca
Table of Contents

Advertisement

Temperature
The temperature measurement is used
only for information or recording purposes,
but not for temperature compensation.
Temperature compensation is carried out
in the sensor.
8.1.8

Hydrogen Peroxide

Hydrogen peroxide as a measured vari‐
able [mA]
Hydrogen peroxide as a measured vari‐
able is measured via one of the two mA
sensor inputs. Temperature compensation
is performed in the sensor. An additionally
connected temperature sensor is only
used for display and data recording with a
data logger and can be issued on a mA-
output via field bus or web server.
Measuring range of the sensors
Select the measuring range. The meas‐
uring range is given on the sensor name‐
plate. An incorrect measuring range leads
to an incorrect measurement.
Temperature
The temperature measurement is used
only for information or recording purposes,
but not for temperature compensation.
Temperature compensation is carried out
in the sensor.
Setting measured variables
8.1.9

Conductivity [mA]

Measured variable conductivity [mA]
When measuring conductivity [mA], use of
a measuring transducer is a prerequisite,
e.g. a measuring transducer DMTa con‐
ductivity. A conductivity sensor cannot be
directly connected to the controller.
Measuring range:
Select the measuring range corre‐
n
sponding to the measuring range of
the measuring transducer used. An
incorrect measuring range leads to an
incorrect measurement.
Temperature:
The temperature measurement is
n
used only for information or recording
purposes, but not however for tem‐
perature compensation. Temperature
compensation is carried out in the
measuring transducer.
Temperature [mA], (as
8.1.10
main measured variable)
Measured variable temperature [mA], (as
main measured variable):
For the measured variable
[mA]' use of a DMTa temperature meas‐
uring transducer or a Pt100V1 measuring
transducer is prerequisite. The measuring
range is: 0 ... 100 °C. A temperature
sensor cannot be connected directly to the
controller.
'Temperature
59