Table 234: Additional Error Information For Error Type "Internal Bus Fault - WAGO -I/O-SYSTEM 750 Manual

Profinet io advanced fieldbus coupler, 2-port switch, 100 mbit/s, digital, analog and complex signals
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

206
Appendix
Table 233:
Byte
Data type
offset
6 / 7
WORD
8 / 9
DWORD
10 / 11
Errors in the internal data bus system are reported on the basis of manufacturer-
specific error type 0x0100. Additional error information is available in the
following table.
Pos : 88.4 /Serie 750 (WAGO-I/O-SYST EM)/Anhang/Kanalspezifisc he Diag nose 1.4 ( 750-375) @ 19\mod_1403859801885_21.doc x @ 156910 @ @ 1
Table 234:
Error Type "Internal bus fault (0x0100)"
Extended
Channel
Error Type
0x0001
0x0003
0x0003
0x0003
0x0003
0x0003
0x0004
0x0005
"ExtChannelDiagnosisData" instance structure
Additional error information for Error Type "Internal bus fault"
Extended
Description
Channel
Additional
value
0x00000106
The module configuration that has been determined on the
internal bus after AUTORESET differs from the configuration
performed before the internal bus fault occurred.
0x01100300
Internal bus protocol error due to internal bus RESET fault.
0x01110300
Internal bus protocol error due to command fault.
0x01120300
Internal bus protocol error due to faulty input data.
0x01140300
Internal bus protocol error due to faulty output data.
0x01180300
Internal bus protocol error caused by timeout.
0x011204xx
Internal bus interruption after module slot xx (xx = 0 ... 250).
0x011005xx
Internal bus initializing error because of an abortive register
communication with the module on slot xx (xx = 1 ... 250).
750-375 PROFINET IO advanced Fieldbus Coupler
Description
0x5802
Manufacturer specific
...
0x7FFF
0x8000 Data transmission impossible
0x8001 Remote mismatch
0x8002 Media redundancy mismatch
0x8003 Sync mismatch
0x8004 Isochronous Mode mismatch
0x8005 Multicast CR mismatch
0x8006 Reserved
0x8007 Fiber optic mismatch
0x8008 Network component function
0x8009 Time mismatch
0x800A
Reserved
...
0xFFFF
Extended Channel Error Type
0x0000
Extended error description, dependent on Error
...
Type
0xFFFF
Extended Channel Additional value
0x00000000
...
Additional description to the error
0xFFFFFFFF
WAGO-I/O-SYSTEM 750
Manual
Version 1.1.0

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-375750-377Wago-i/o-system 750 series

Table of Contents