Evaluating The Fieldbus Status; Table 55: Fieldbus Diagnostics - Solution In Event Of Error - WAGO -I/O-SYSTEM 750 Manual

Profinet io advanced fieldbus coupler, 2-port switch, 100 mbit/s, digital, analog and complex signals
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Pos : 70.9 /Serie 750 (WAGO-I/O-SYST EM)/Di agnose/Fel dbus koppl er/-contr oller/F eldbusstatus aus werten (RUN, BF , DIA) (750-375, -377) @ 13\mod_1353592473713_21.doc x @ 106832 @ 3 @ 1
10.1.1

Evaluating the Fieldbus Status

The top three LEDs (RUN, BF and DIA) are used to indicate the operating status
of PROFINET IO communication.
Table 55: Fieldbus diagnostics – solution in event of error
LED
Status
RUN
green
green
flashing
OFF
BF
green
flashing
red
red
flashing
OFF
DIA
red
The integrated LNK and ACT LEDs display the physical fieldbus connection and
network activity on the RJ-45 fieldbus connections directly.
Manual
Version 1.1.0
Explanation
The power supply is ON.
Part of or the entire fieldbus node
is in energy-saving mode or output
mode due to the PROFIenergy
"Start Pause" command.
The power supply is OFF.
1 Hz, pulse-no-pulse ratio 1:1 (for
3 sec.):
Node flashing test (DCP Control
Signal FlashOnce).
With repetitive node flashing tests
in succession, the indicator light
can briefly capture the status of the
group fault display (red).
There is no ETHERNET
connection (link).
There is an ETHERNET
connection on at least one port. A
PROFINET connection (IOAR) is
not established.
At lease on application relationship
has been established to an IO
controller (IOAR).
Parameterization error, module
differences or diagnostics display.
Evaluating the diagnostics display!
A detailed description of the diagnostics display analysis is
available in the chapter "PROFINET IO Diagnostics"!
Solution
-
1. Use the PROFIenergy "End Pause"
command to exit energy-saving
modes.
1. Check the power supply
(24 V, 0 V).
-
1. Check the network cable.
1. Check the connection between IO
controller and IO device.
2.
Check if the right device name has
been assigned for the IO device.
3. Check if the connected network
infrastructure ETHERNET link is
100 Mbit/s full-duplex compliant.
-
1. Check the parameter settings and
fieldbus node setup or evaluate the
diagnostics display.
Diagnostics
115