Digital Output Modules With Diagnostics (Do, Dia); Table 119: Parameterization - Overview Of Additional Attributes For Digital Output Modules With Diagnostics (Do, Dia); Table 120: Parameterization Do, Dia - Attribute "Channel Diagnosis; Table 121: Parameterization Do, Dia - Attribute "Diagnosis: External Fault - WAGO -I/O-SYSTEM 750 Manual

Profinet io advanced fieldbus coupler, 2-port switch, 100 mbit/s, digital, analog and complex signals
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
14.2.3

Digital Output Modules with Diagnostics (DO, DIA)

If the digital output module provides diagnostic data, the following attributes can
also be set channel-by-channel during parameterization.
Table 119: Parameterization – Overview of Additional Attributes for Digital Output Modules with
Diagnostics (DO, DIA)
Additional Attributes for Digital Output Modules with Diagnostics (DO, DIA)
-
Channel diagnosis (additionally)
-
Diagnosis: External fault (additionally)
-
Diagnosis: Short circuit" (additionally)
-
Diagnosis: Line break (additionally)
Table 120: Parameterization DO, DIA – Attribute "Channel diagnosis"
Attribute Name
Channel diagnosis
Table 121: Parameterization DO, DIA – Attribute "Diagnosis: External fault"
Attribute Name
Diagnosis: External
fault
Table 122: Parameterization DO, DIA – Attribute "Diagnosis: Short circuit"
Attribute Name
Diagnosis: Short
circuit
Manual
Version 1.1.0
Attribute Value
Description
Any errors that may occur on the respective signal
channel do not cause transmission of a diagnostic
0 (false)
alarm nor entry in the diagnostics database of the
station proxy.
Any errors that may occur on the respective signal
channel and the error type explicitly released entail
1 (true)
transmission of a diagnostic alarm. The respective
error leads to an entry in the diagnostics database
of the station proxy.
Attribute Value
Description
An external error on the respective signal channel
does not cause transmission of a diagnostic alarm
0 (false)
nor entry in the diagnostics database of the station
proxy.
Provided that the channel diagnostics of the
respective signal channel has been activated, an
external error leads to transmission of a diagnostic
1 (true)
alarm and entry in the diagnostics database of the
station proxy.
Attribute Value
Description
A short circuit on the respective signal channel
does not lead to transmission of a diagnostic alarm
0 (false)
nor to entry in the diagnostics database of the
station proxy.
Provided that the channel diagnostics of the
respective signal channel has been activated, a
1 (true)
short circuit leads to transmission of a diagnostic
alarm and entry in the diagnostics database of the
station proxy.