WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
7.6.1.2
Example of Packaging Digital Information
In addition to the fieldbus coupler (DAP), a station consists of the following I/O
modules in the order shown:
Table 36: Example for a station with the following selected submodules
Slot
0
1
2
3
4
5
6
The digital submodule at slot 1 allocates a total of 2 bytes in the input process
image and occupies 2 bits of that.
The digital submodule at slot 2 allocates a total of 2 bytes in the output process
image and occupies 4 bits of that.
There is an analog output submodule at slot 3 that plays no role in packaging
digital I/O modules.
The digital submodule at slot 4 requires 8 bits that are included in the output data
area allocated from slot 2. 4 bits of slot 2 are still available for additional output
data.
The digital submodule at slot 5 requires 4 bits that are included in the input data
area allocated by slot 1. 10 bits are still available from slot 1 for additional input
data.
The digital submodule at slot 6 allocates an additional output data area of 1 byte.
The area of slot 2 is closed and remains unused. The free bits do not reach the
peripherals.
The figures below show the packaged user data in the real-time PROFINET IO
telegram each in the output and input direction.
Figure 40: Output process data in the frame IOC IOD
Figure 41: Input process data in the frame IOD IOC
Manual
Version 1.1.0
Module
Fieldbus coupler PROFINET IO
75x-401 2DI
75x-504 (/0..-...) 4DO
75x-550 2AO, 0-10V
75x-530 (/0..-...) 8DO
75x-403 4DI
75x-501(/0..-...) 2DO
Function Description
Submodule
2DI (+ 14 BIT I)
4DO (+ 12 BIT O)
INT16[4] O
8DO (- 8 BIT O)
4DI (- 4 BIT I)
2DO (+ 6 BIT O)
83