Function Description
7.4

Process Data Architecture

Pos : 63.6.1 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbil d/Prinzi pieller Aufbau ( Koppl er) PR OFIBUS/PR OFIN ET @ 10\mod_1308737518759_21.doc x @ 74010 @ 3 @ 1
7.4.1

Basic Structure

A node can consist of a mixed arrangement of analog and digital, system and
special function modules.
For the configuration only I/O modules are taken into account, which exchange
process data on the internal bus (K-Bus) with the fieldbus coupler (data width or
bit width greater than 0).
Pos : 63.6.2 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbil d/D as l okale Proz ess abbil d liegt ers t nac h dem erfolgreic hen Ver bindungs aufbau vor. (PR OFIN ET) @ 16\mod_1372755013725_21.doc x @ 125310 @ @ 1
The input and output process images which are exchanged with the respective
IOC using real time frames are only available on a successful connection
establishment to the particular IOC.
Pos : 63.6.3 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbil d/Infor mation: Anzahl der Ei n- und Ausg angs bits bz w. -bytes [...] entnehmen Si e Bus kl emmenbeschr eibung @ 6\mod_1256034203734_21.doc x @ 43146 @ @ 1
Additional Information
For the number of input and output bits or bytes of the individual I/O modules,
refer to the corresponding description of the I/O modules.
Pos : 63.6.4 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbil d/F ür das lokale Pr oz ess abbild, Daten i n der R ei henfolge i hrer Position ( 375, 377) @ 13\mod_1354638504422_21.doc x @ 107318 @ @ 1
For the local input and output process data image, the data of the configured I/O
modules is stored in the order of its position next to the fieldbus coupler in the
respective process image.
The size of the process image is determined by the configuration data of the
fieldbus coupler and of the I/O modules connected to it.
If the maximum size is exceeded in the respective process image, an error
message appears in the configuration software being used.
Pos : 63.6.5 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbil d/Proz ess abbild PR OFIN ET IO ( 750-375) max. 512 Byte @ 15\mod_1368440591989_21.doc x @ 119494 @ @ 1
The process image is limited to 512 bytes of input or output data. Thus, up to 250
I/O modules can be connected to the fieldbus coupler until the process image
reaches a maximum size of 512 bytes in the input and/or in the output direction.
Pos : 63.6.6 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbil d/Infor mation: Weitere Infor mati onen z ur Begrenzung der Konfig urati onsdaten! @ 19\mod_1403525288296_21.doc x @ 156368 @ @ 1
More information on configuration limits!
For additional information to the configuration limits refer to "Configuration
limits" chapter.
Pos : 63.6.7 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbil d/Z uor dnung der Ein- und Ausgangsdaten (750- 375, -377, Koppl er) @ 13\mod_1354638714063_21.doc x @ 107337 @ 4 @ 1
750-375 PROFINET IO advanced Fieldbus Coupler
WAGO-I/O-SYSTEM 750