Table 194: Parameterization AO, PE – Attribute "Minimal pause time"
Attribute Name
Minimal pause time
Table 195: Parameterization DO, PE – Attribute "Pause output value"
Attribute Name
Pause output value

14.2.11 Specialty Modules

Nearly all special-purpose modules receive a parameter data set in the form of a
record write request to the data set number or index 0x4000 or 16384.
This data set receives the following attributes.
Table 196: Parameterization SF, DIA – Attribute "Channel diagnosis"
Attribute Name
Channel diagnosis
Table 197: Parameterization SF, DIA – Attribute "Diagnosis: External fault"
Attribute Name
Diagnosis: External
fault
750-375 PROFINET IO advanced Fieldbus Coupler
Attribute Value
Description
10 s
Pauses requested by the PROFIenergy profile are
only introduced during pause times greater than or
1 min
equal to the setting made. If a PROFIenergy
10 min
submodule has been configured from the station
1 h
proxy, the setting made here for the respective
10 h
output module has no meaning.
1 d
infinite
Attribute Value
Description
If the requested pause time of the PROFIenergy
0 ... 32767
"Start_Pause" command is greater than or equal to
-32767 ... 0 ... 32767
the parameterized "Minimum pause time", the
0 ... 65535
respective output channel outputs the specified
pause output value.
Attribute Value
Description
An error on the respective signal channel does not
lead to transmission of a diagnostic alarm nor entry
0 (false)
in the diagnostics database of the station proxy.
An error on the respective signal channel leads to
transmission of a diagnostic alarm. The respective
1 (true)
error leads to an entry in the diagnostics database
of the station proxy.
Attribute Value
Description
An external fault on the respective signal channel
does not cause transmission of a diagnostic alarm
0 (false)
nor entry in the diagnostics database of the station
proxy.
Provided that the channel diagnostics of the
respective signal channel has been activated, an
external fault leads to transmission of a diagnostic
1 (true)
alarm and entry in the diagnostics database of the
station proxy.