WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Table 242: Structure of the erroneously configured submodules
Byte
Data type
offset
0 / 1
WORD
2 / 3
DWORD
4 / 5
6 / 7
WORD
8 / 9
WORD
Manual
Version 1.1.0
Description
0x00
0x01
Subslot with odd submodule
0x00
0x00
Identification of the plugged submodule
(SubmoduleIdentNumber)
0x00
0x00
Submodule state (Submodulstate.b15 = 0)
0x0000
0x0001
0x0002
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
...
0x7FFF
Submodule state (Submodule state.b15 = 1)
'000'
'001'
b0
...
'010'
b2
...
'111'
b3
b4
b5
b6
No submodule present
Wrong submodule
Submodule locked by IO controller
Reserved
Application ready pending
Reserved
Reserved
Submodule substituted
Reserved
---
The submodule is not available for takeover
by IOSAR.
Reserved
0
No channel of the submodule contains
"QualifiedChannelDiagnosis".
1
At least one channel of the submodule
contains "QualifiedChannelDiagnosis".
0
No channel of the submodule requires
maintenance.
1
At least one channel of the submodule
demands maintenance.
0
No channel of the submodule demands
maintenance.
1
At least one submodule channel demands
maintenance.
0
There is no diagnosis data available/stored for
this submodule.
1
There is diagnosis data available for this
submodule: It can be read with the
corresponding records.
Appendix