WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
All other errors are supplied with extended error type 0x0001 and additional value
0x00000000.
Pos : 88.5 /Serie 750 (WAGO-I/O-SYST EM)/Anhang/Kanalspezifisc he Diag nose 1.5 ( 750-375, - 377) @ 19\mod_1403859811400_21.doc x @ 156918 @ 45555553 @ 1
14.5.1.1
1.3.1.1
The following lists contain the respective error types and their meaning for I/O
modules with diagnostics capability sorted by digital input/output modules, analog
input/output modules and complex I/O modules.
14.5.1.1.1 Digital Input Modules
Table 235: Fault cases of digital input modules with diagnostics capability
Item
number
75x-418,
75x-419,
75x-421
75x-425
75x-439
14.5.1.1.2 Digital Output Modules
Table 236: Fault cases of digital output modules with diagnostics capability
Item
number
75x-506 BIT
75x-507,
75x-532,
75x-537
75x-522,
750-523
Manual
Version 1.1.0
Fault Cases of I/O Modules with Diagnostics Capability
Data
Error type
format
BIT
0x001A / 26
BIT
0x001A / 26
Data
Error type
format
0x0001 / 1
0x0002 / 2
0x0006 / 6
BIT
0x001A / 26
BIT
0x001A / 26
Explanation
External fault
Short circuit of the transmitter power
supply
External fault
Signal line to transmitter interrupted or
short circuit
Explanation
Short circuit
Signal output short circuit
Overvoltage
Field voltage to the signal output
inadequate,
Line break
signal line to the actuator interrupted or
not connected
External fault
Short circuit of the signal output against
+24V or GND, signal line to the actuator
is interrupted or not connected or excess
temperature through overloading.
External fault
External fault (broken wire, overload or
short circuit, manual operation)
Appendix
207