2-Channel Pulse Width Modules; Distance And Angle Measurement Modules; Table 87: Module Types - 2-Channel Pulse Width Output Modules; Table 88: Submodule Types And Data Lengths - 2-Channel Pulse Width Output - WAGO -I/O-SYSTEM 750 Manual

Profinet io advanced fieldbus coupler, 2-port switch, 100 mbit/s, digital, analog and complex signals
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

164
Appendix
14.1.6.2

2-Channel Pulse Width Modules

The group of 2-channel pulse width output module has one module type divided
into two submodule types.
Table 87: Module types – 2-Channel Pulse Width Output Modules
2PWM
Module type
2PWM
Pulse width output modules receive the provider status (IOPS) from the IO
controller and supply it with the consumer status (IOCS) of the received output
information in case only the actual user data is exchanged. If all existing
information is available in the process image of the inputs and outputs, the process
data qualifiers are also transmitted in the opposite direction.
Table 88: Submodule types and data lengths – 2-Channel Pulse Width Output Module
PNIO module type
PNIO submodule type
2PWM
INT16[2] O
{UINT8, INT16}[2] I/O
14.1.6.3

Distance and Angle Measurement Modules

The group of distance and angle measurement modules includes three module
types:
Table 89: Module types – Distance and Angle Measurement Modules
Module type
1SSI
Module type
1ENC
Module type
1DII
For the distance and angle measurement modules, the provider and consumer
status (IOPS, IOCS) of the input or output information are exchanged between the
IO controller and IO device in both directions. With the SSI interface 75x-630,
there is also an option to transmit the input data of the transmitter only.
750-375 PROFINET IO advanced Fieldbus Coupler
Description
2-Channel Pulse Width Output Modules,
16 bits output data per signal channel
Data type
Integer16
{Unsigned8,
Unsigned16}
Description
SSI Transmitter Interface,
32 bits input data
Description
Incremental Encoder Interface,
32 bits input and output data plus control byte
and status byte per signal channel, access to the
register structure via cyclic data exchange
Description
Digital Impulse Interface,
24 bits input and output data plus control byte
and status byte per signal channel, access to the
register structure via cyclic data exchange
WAGO-I/O-SYSTEM 750
Substitute I/O modules
75x-511,
plus all variations
Process data length [byte]/
allocation [bit]
Input (I-PI) Output (O-PI)
0
4
6
6
Substitute I/O modules
75x-630,
plus all variations
Substitute I/O modules
75x-631, 75x-634, 75x-637,
plus all variations
Substitute I/O modules
75x-635
Telegram
allocation [byte]
Input
Output
1
5
8
8