WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Table 173: Parameterization AI, 3 PM – Attribute "Min./Max. reset interval [200ms]"
Attribute Name
Min./Max. reset
interval [200ms]
14.2.7

Analog Output Module (AO)

All analog output modules receive a parameter data set from the IO controller in
the form of a record write request.
For standard modules, the parameter data set is intended for the data set number
or index 0x4000 or 16384.
This data set receives the following attributes.
Table 174: Parameterization – Overview of Attributes for Analog Output Modules (AO)
Attributes for Analog Output Modules (AO)
-
Substitute value behavior
-
Substitute value (2 Byte)
Table 175: Parameterization AO – Attribute "Substitute value behavior"
Attribute Name
Substitute value
behavior
Manual
Version 1.1.0
Attribute Value
Description
See manual for I/O module 75x-494, 75x-495
0 ... 10 ... 254
www.wago.com
Attribute Value
Description
If an established AR is disconnected to which the
submodule is assigned or when the status of the
"Provider State Flag" changes in the APDU status
of the consumer telegram from "RUN" to "STOP",
according to device
the parameterized substitute value behavior of the
settings
station proxy is applied for the duration of missing
output data. The parameterized substitute value of
the respective output channel has no meaning in
this context.
If an established AR is disconnected to which the
submodule is assigned or when the status of the
"Provider State Flag" changes in the APDU status
of the consumer telegram from "RUN" to "STOP",
keep last valid value
the last valid status of the respective output channel
is retained for the duration of the missing output
data. The parameterized substitute value of the
respective output channel has no meaning in this
context.
If an established AR is disconnected to which the
submodule is assigned or when the status of the
"Provider State Flag" changes in the APDU status
set substitute value
of the consumer telegram from "RUN" to "STOP",
the parameterized substitute value of the respective
output channel is output for the duration of the
missing output data.
Appendix
187