750-375 PROFINET IO advanced Fieldbus Coupler
8.6.1.4

Response to PROFINET IO failure

Table 43: Parameterization DAP – Attribute Response to PROFINET IO failure
Attribute Name
Response to
PROFINET IO failure
8.6.1.5

Response to K-Bus failure

Table 44: Parameterization DAP – Attribute Response to K-Bus failure
Attribute Name
Response to K-Bus
failure
8.6.1.6

Activation of the integrated Webserver

Table 45: Parameterization DAP – Attribute Webserver
Attribute Name
Webserver
(TCP Port 80)
The web server of the fieldbus coupler is disabled by default and can only be
enabled by the DAP parameterization data set.
Activity is terminated after any hardware or software reset of the fieldbus coupler.
8.6.1.7

Activation of Firmware Updates

Table 46: Parameterization DAP – Attribute WAGO-Service (TCP Port 6626)
Attribute Name
WAGO Service
(TCP Port 6626)
The WAGO service port of the fieldbus coupler is enabled by default and can only
be disabled by the DAP parameterization data set.
Manual
Version 1.1.0
Attribute Value
Description
For all output submodules parameterized
Output image is
"according to device settings" (default), the output
stored
data last valid before the fault remains valid.
Substitute values
The substitute values parameterized on the part of
are switched
the output submodules are output.
For all output submodules parameterized
Output image is
"according to device settings" (default), the output
cleared
data is set to zero.
Attribute Value
Description
Any existing IO controller application relationships
PROFINET IO
(IOAR) are terminated.
communication is
stopped
Existing IO controller application relationships
Input image gets
(IOAR) are not terminated. However, the process
invalid
data qualifiers of all provider (IOPS) and consumer
data (IOCS) are set to the "BAD" status.
Attribute Value
Description
TCP/UDP port 80 is disabled.
0 (false)
The web server is inaccessible.
TCP/UDP port 80 is enabled.
1 (true)
The web server is accessible.
Attribute Value
Description
WAGO TCP service port 6626 is disabled. The
0 (false)
device software cannot be updated by a firmware
update via ETHERNET.
WAGO TCP service port 6626 is enabled. The
1 (true)
device software can be updated by a firmware
update via ETHERNET.
Commissioning
101