Table 113: Parameterization - Overview Of Attributes For Digital Input Modules; Table 114: Parameterization Di, Dia - Attributes "Channel Diagnosis; Table 115: Parameterization Di, Dia - Attributes "Diagnosis: External Fault - WAGO -I/O-SYSTEM 750 Manual

Profinet io advanced fieldbus coupler, 2-port switch, 100 mbit/s, digital, analog and complex signals
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Table 113: Parameterization – Overview of Attributes for Digital Input Modules with Diagnostics
(DI, DIA)
Attributes for Digital Input Modules with Diagnostics (DI, DIA)
-
Channel diagnosis
-
Diagnosis: External fault
Table 114: Parameterization DI, DIA – Attributes "Channel diagnosis"
Attribute Name
Channel diagnosis
Table 115: Parameterization DI, DIA – Attributes "Diagnosis: External fault"
Attribute Name
Diagnosis: External
fault
Manual
Version 1.1.0
Attribute Value
Description
Any errors that may occur on the respective signal
channel do not cause transmission of a diagnostic
0 (false)
alarm nor entry in the diagnostics database of the
station proxy.
Any errors that may occur on the respective signal
channel and the error type explicitly released entail
1 (true)
transmission of a diagnostic alarm. The respective
error leads to an entry in the diagnostics database
of the station proxy.
Attribute Value
Description
An external error on the respective signal channel
does not cause transmission of a diagnostic alarm
0 (false)
nor entry in the diagnostics database of the station
proxy.
Provided that the channel diagnostics of the
respective signal channel has been activated, an
external error leads to transmission of a diagnostic
1 (true)
alarm and entry in the diagnostics database of the
station proxy.
Appendix
173

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-375750-377Wago-i/o-system 750 series

Table of Contents