Gsd File; Parameterization; Parameterization Of The Station Proxy (Dap) - WAGO -I/O-SYSTEM 750 Manual

Profinet io advanced fieldbus coupler, 2-port switch, 100 mbit/s, digital, analog and complex signals
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
8.5

GSD File

The GSD file describes the properties of the fieldbus coupler and I/O modules
required for a configuration such as the data length in the respective process
image or the parameter data.
This file is created by the device manufacturers and made available to the user.
The GSD file is required to configure the IO controller for active data exchange
with the fieldbus coupler. It is imported or installed into the configuration
software.
An XML-based language, GSDML is used as the language for the device
description file.
Structure, content and coding of this device master data are standardized so the
software of various manufacturers can be used for the configuration.
More information on the GSD files
The GSD file can be obtained at www.wago.com.
When installing this file, please refer to the information provided in the
documentation of the configuration software which you are using.
Pos : 65.3 /Serie 750 (WAGO-I/O-SYST EM)/In Betrieb nehmen/Fel dbus knoten i n Betrieb nehmen/PROFIBU S/Par ametrierung (750-375, -377) @ 14\mod_1361262630450_21.doc x @ 112276 @ 23444444443 @ 1
8.6

Parameterization

Before data can be exchanged between IO controller and IO device,
parameterization is required in addition to the hardware configuration in the
configuration software. The default attribute values are highlighted in "bold".
The configuration is used to set the parameters (attributes) for the fieldbus coupler
as a station proxy (DAP) and for the I/O modules based on the device description
(GSD). The individual parameters are set via selectable textual descriptions.
8.6.1

Parameterization of the Station Proxy (DAP)

The following list provides an overview of configurable attributes for the station
proxy and descriptions of the individual parameters are listed in the subsequent
chapter.