202
Appendix
14.5
Structure of the Standardized Diagnosis Data Sets
The diagnosis data sets consist of several structures.
The first element in the data set is the head of the structure. It describes the
version and the length of the following data. The "BlockType" specifies the
structure and content of the data set. The following "BlockTypes" are used by the
fieldbus coupler.
Table 230: "BlockTypes"
BlockType
0x0010
0x8104
The head of the structure has a length of 6 bytes and is structured as follows:
Table 231: Head of the structure
Byte
Data type
offset
0 / 1
WORD
2 / 3
WORD
BYTE
4/5
BYTE
The version of the data set is 1.1. As a consequence the existing Application
process idenficator (API) is always set to zero (default API) and has a data length
of 4 bytes.
14.5.1
Extended Channel Diagnostics
The "BlockType" in the head structure corresponds to the value for a diagnostic
data set (0x0010). The length of the data set results from the following diagnostic
objects for fault submodules or channels.
The diagnostic entries are initiated by a "ExtChannelDiagnosis" structure. The
respective "ExtChannelDiagnosisData" diagnostic objects then follow for the
respective submodules or channels. The "ExtChannelDiagnosis" structure has a
size of 14 bytes and is structured as follows.
Pos : 88.2 /Serie 750 (WAGO-I/O-SYST EM)/Anhang/Kanalspezifisc he Diag nose 1.2 ( 750-375) @ 19\mod_1403859760031_21.doc x @ 156898 @ @ 1
750-375 PROFINET IO advanced Fieldbus Coupler
Description
Diagnostic data
Real/expected configuration mismatch
Description
Content of the "BlockType" data set
0x0010
0x8104
Length of the data set in bytes (BlockLength)
0x01
BlockVersion (major) = 1
0x01 BlockVersion (minor) = 1
WAGO-I/O-SYSTEM 750
Diagnostic data set
Configuration data set specified/actual
deviation
Including length of the version in
bytes
Version 1.1.0
Manual