Table 63: Blink Code Table For The 'I/O' Led Signaling, Error Code 6; Table 64: Blink Code Table For The 'I/O' Led Signaling, Error Code 7; Table 65: Blink Code Table For The I/O Led Signaling, Error Code 9; Table 66: Blink Code Table For I/O Led Signaling, Error Code 10 - WAGO -I/O-SYSTEM 750 Manual

Profinet io advanced fieldbus coupler, 2-port switch, 100 mbit/s, digital, analog and complex signals
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler

Table 63: Blink code table for the 'I/O' LED signaling, error code 6

Error code 6: -not used-
Error
Argument
-
Pos : 70.15 /Serie 750 ( WAGO-I/O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 7...8 (Fehlerc ode nic ht g enutz t) @ 9\mod_1281702273781_21.doc x @ 63680 @ @ 1

Table 64: Blink code table for the 'I/O' LED signaling, error code 7...8

Error code 7...8: -not used-
Error
Argument
-
Pos : 70.16 /Serie 750 ( WAGO-I/O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 9 ( 750-0333, -806, -842, - 843, -833) @ 9\mod_1281702354591_21.doc x @ 63684 @ @ 1

Table 65: Blink code table for the I/O LED signaling, error code 9

Error code 9: "CPU Trap error"
Error
Argument
1
2
3
4
Pos : 70.17 /Serie 750 ( WAGO-I/O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 10...11 (Fehl ercode nic ht genutzt) @ 11\mod_1320767624985_21.doc x @ 82894 @ @ 1

Table 66: Blink code table for I/O LED signaling, error code 10...11

Error code 10...11: -not used-
Error
argument
-
Pos : 70.18 /Serie 750 ( WAGO-I/O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 12 (750- 333) @ 11\mod_1320768612069_21.doc x @ 82958 @ @ 1

Table 67: Blink code table for I/O LED signaling, error code 12

Error code 12 "Initialization error, internal bus"
Error
Argument
n*
* The number of light pulses (n) indicates the position of the I/O module.
I/O modules without data are not counted (e.g. supply modules without diagnostics)
Pos : 70.19 /Serie 750 ( WAGO-I/O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Vers orgungss pannungsstatus aus werten ( alle Koppler/C ontroll er) @ 6\mod_1259230026625_21.doc x @ 45546 @ 3 @ 1
Manual
Version 1.1.0
Error Description
Solution
Not used
Error Description
Solution
Not used
Error Description
Solution
Illegal Opcode
Stack overflow
Fault in the program sequence.
1. Please contact the I/O Support.
Stack underflow
NMI
Error description
not used
Error description
Error with parameter
communication during
internal bus initialization
Remedy
Remedy
1. Switch off the power for the node.
2. Ensure that the nth module with process data is
supplied with power at the field side.
3. Switch the power on.
Diagnostics
-
123

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-375750-377Wago-i/o-system 750 series

Table of Contents