Table 82: Submodule Types And Data Lengths - Analog Input Modules - WAGO -I/O-SYSTEM 750 Manual

Profinet io advanced fieldbus coupler, 2-port switch, 100 mbit/s, digital, analog and complex signals
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Analog input modules receive the consumer status (IOCS) from the I/O controller
and supply it with the provider status (IOPS) of the existing input information if
only the actual user data is replaced. If all existing information is available in the
process image of the inputs and outputs, the process data qualifiers are also
transmitted in the opposite direction.
Table 82: Submodule types and data lengths – Analog Input Modules
PNIO module type
PNIO submodule type
2AI
INT16[2] I
{UINT8, INT16}[2] I/O
2AI HART (from FW 03)
{INT16, FLOAT32}[2] I {Integer16,
{INT16, FLOAT32[2]}[2]
I
{INT16, FLOAT32[3]}[2]
I
{INT16, FLOAT32[4]}[2]
I
3AI
{UINT8, UINT8,
INT16}[8] I/O
4AI
INT16[4] I
{UINT8, INT16}[4] I/O
8AI
INT16[8] I
{UINT8, INT16}[8] I/O
3PMM
{UINT8, INT8[23]} I/O
Manual
Version 1.1.0
Process data length [byte]/
allocation [bit]
Data type
Input (I-PI) Output (O-PI)
Integer16
4
{Unsigned8,
6
Integer16}
12
Float32}
{Integer16,
20
Float32[2]}
{Integer16,
28
Float32[3]}
{Integer16,
36
Float32[4]}
{Unsigned8,
Unsigned8,
12
Integer16}
Integer16
8
{Unsigned8,
12
Integer16}
Integer16
16
{Unsigned8,
24
Integer16}
{Unsigned8,
Unsigned8[23]
24
}
Appendix
Telegram
allocation [byte]
Input
Output
0
5
6
8
0
13
0
21
0
29
0
37
12
14
0
9
12
14
0
17
24
26
24
26
161
1
8
1
1
1
1
14
1
14
1
26
26

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-375750-377Wago-i/o-system 750 series

Table of Contents