Profienergy Submodules (Do, Pe); Table 123: Parameterization Do, Dia - Attribute "Diagnosis: Line Break; Table 124: Parameterization - Overview Of Additional Attributes For Profienergy Submodules (Do, Pe); Table 125: Parameterization Do, Pe - Attribute "Minimal Pause Time - WAGO -I/O-SYSTEM 750 Manual

Profinet io advanced fieldbus coupler, 2-port switch, 100 mbit/s, digital, analog and complex signals
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

176
Appendix
Table 123: Parameterization DO, DIA – Attribute "Diagnosis: Line break"
Attribute Name
Diagnosis: Line break
14.2.4

PROFIenergy Submodules (DO, PE)

When configuring PROFIenergy submodules, an additional parameter data set is
sent to the data se number or index 0x5000 or 20480.
Regarding the PROFIenergy properties, the following attributes can also be
specified during parameterization.
Table 124: Parameterization – Overview of Additional Attributes for PROFIenergy Submodules
(DO, PE)
Additional Attributes for PROFIenergy Submodules (DO, PE)
-
Minimal pause time (additionally)
-
Pause output state (additionally)
Table 125: Parameterization DO, PE – Attribute "Minimal pause time"
Attribute Name
Minimal pause time
Table 126: Parameterization DO, PE – Attribute "Pause output state"
Attribute Name
Pause output state
750-375 PROFINET IO advanced Fieldbus Coupler
Attribute Value
Description
A line break on the respective signal channel does
not lead to transmission of a diagnostic alarm nor
0 (false)
to entry in the diagnostics database of the station
proxy.
Provided that the channel diagnostics of the
respective signal channel has been activated, a line
1 (true)
break leads to transmission of a diagnostic alarm
and entry in the diagnostics database of the station
proxy.
Attribute Value
Description
10 s
Pauses requested by the PROFIenergy profile are
only introduced during pause times greater than or
1 min
equal to the setting made. If a PROFIenergy
10 min
submodule has been configured from the station
1 h
proxy, the setting made here for the respective
10 h
output module has no meaning.
1 d
infinite
Attribute Value
Description
If the requested pause time of the PROFIenergy
"Start_Pause" command is greater than or equal to
0 (false)
the parameterized "Minimum pause time", the
respective output channel outputs status '0'.
If the requested pause time of the PROFIenergy
"Start_Pause" command is greater than or equal to
1 (true)
the parameterized "Minimum pause time", the
respective output channel outputs status '1'.
WAGO-I/O-SYSTEM 750
Manual
Version 1.1.0