Special Ao Module Types With Parameter Channel; Table 181: Parameterization Ao, Dia - Attribute "Diagnosis: Overtemperature; Table 182: Parameterization Ao, Dia - Attribute "Diagnosis: Error; Table 183: Parameterization Ao, Dia - Attribute "Diagnosis: External Fault - WAGO -I/O-SYSTEM 750 Manual

Profinet io advanced fieldbus coupler, 2-port switch, 100 mbit/s, digital, analog and complex signals
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-375 PROFINET IO advanced Fieldbus Coupler
Table 181: Parameterization AO, DIA – Attribute "Diagnosis: Overtemperature"
Attribute Name
Diagnosis:
Overtemperature
Table 182: Parameterization AO, DIA – Attribute "Diagnosis: Error"
Attribute Name
Diagnosis: Error
Table 183: Parameterization AO, DIA – Attribute "Diagnosis: External fault"
Attribute Name
Diagnosis: External
fault
14.2.9
Special AO Module Types with Parameter Channel (AO,
562, 563)
For standard modules equipped with a parameter channel, another parameter data
set is sent to the data set number or index 0x2000 or 8192.
Depending on the I/O module type (item number), the following additional
attributes can then be set during parameterization.
Manual
Version 1.1.0
Attribute Value
Description
An overtemperature in the output driver of the
respective signal channel does not lead to
0 (false)
transmission of a diagnostic alarm nor entry in the
diagnostics database of the station proxy.
An overtemperature in the output driver of the
respective signal channel leads to transmission of a
1 (true)
diagnostic alarm. The respective error leads to an
entry in the diagnostics database of the station
proxy.
Attribute Value
Description
An external or internal error on the respective
signal channel does not cause transmission of a
0 (false)
diagnostic alarm nor entry in the diagnostics
database of the station proxy.
An error on the respective signal channel leads to
transmission of a diagnostic alarm. The respective
1 (true)
error leads to an entry in the diagnostics database
of the station proxy.
Attribute Value
Description
An external fault on the respective signal channel
does not cause transmission of a diagnostic alarm
0 (false)
nor entry in the diagnostics database of the station
proxy.
An external fault on the respective signal channel
leads to transmission of a diagnostic alarm. The
1 (true)
respective error leads to an entry in the diagnostics
database of the station proxy.
Appendix
189