Table 60: Blink Code Table For I/O Led Signaling, Error Code 6; Table 61: Blink Code Table For The I/O Led Signaling, Error Code 7; Table 62: Blink Code Table For The 'I/O' Led Signaling, Error Code 8 - WAGO 750-325 Manual

Cc-link fieldbus couplerб 156 kbaud ... 10 mbaud; digital and analog signals
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler

Table 60: Blink Code Table for I/O LED Signaling, Error Code 6

Error code 6: "Node configuration error"
Error
Argument
1
2
3
4
5

Table 61: Blink Code Table for the I/O LED Signaling, Error Code 7

Error code 7: "Not supported I/O module"
Error
Argument
n

Table 62: Blink Code Table for the 'I/O' LED Signaling, Error Code 8

Error code 8: -not used-
Error
Argument
-
Error Description
Solution
1.
2.
Too many analog
output signals for the
remote register area
3.
(RWw).
4.
1.
2.
Too many analog
input signals for the
remote register area
3.
(RWr).
4.
1.
2.
Too many digital
output signals for the
remote I/O area (RY).
3.
4.
1.
2.
Too many digital
input signals for the
remote I/O area (RX).
3.
4.
1.
Protocol version
2.
conflict
3.
Error Description
Solution
1.
First unsupported
2.
I/O module
in place of n.
3.
Error Description
Solution
Not used
Turn off the power supply for the node.
Reduce the number of I/O modules with analog output data
or increase the number of stations or cycles using DIP
switches 4/5 or 6/7.
Turn the power supply on again.
Does the error persist?
Repeat steps 1 through 3.
Turn off the power supply for the node.
Reduce the number of I/O modules with analog input data
or increase the number of stations or cycles using DIP
switches 4/5 or 6/7.
Turn the power supply on again.
Does the error persist?
Repeat steps 1 through 3.
Turn off the power supply for the node.
Reduce the number of I/O modules with digital output data
or increase the number of stations or cycles using DIP
switches 4/5 or 6/7.
Turn the power supply on again.
Does the error persist?
Repeat steps 1 through 3.
Turn off the power supply for the node.
Reduce the number of I/O modules with digital input data or
increase the number of stations or cycles using DIP
switches 4/5 or 6/7.
Turn the power supply on again.
Does the error persist?
Repeat steps 1 through 3.
Turn off the power supply for the node.
Change the operating mode using DIP switch 8.
Turn the power supply on again.
Turn off the power supply to the node.
Replace the nth I/O module containing process data or
reduce the number of modules to the number of n-1.
Turn the power supply on.
Diagnostics 105
Manual
Version 2.0.1

Advertisement

Table of Contents
loading