3.6.3

Field Supply

Pos : 19.13.23 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Ans chl uss @ 3\mod_1232950082031_21.doc x @ 26696 @ 4 @ 1
3.6.3.1

Connection

Sensors and actuators can be directly connected to the relevant channel of the I/O
module in 1, 2, 3 or 4 conductor connection technology. The I/O module supplies
power to the sensors and actuators. The input and output drivers of some I/O
modules require the field side supply voltage.
Pos : 19.13.24 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Ans chl uss - Ei nspeis ung fel dsei tig (Standard + er weiterter ECO) @ 3\mod_1232950087703_21.doc x @ 26712 @ @ 1
The fieldbus coupler/controller provides field side power (DC 24 V). In this case
it is a passive power supply without protection equipment.
Pos : 19.13.25 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Ans chl uss - Potentialgruppen mit Eins peisekl emme @ 3\mod_1232950090437_21.doc x @ 26720 @ @ 1
Power supply modules with or without fuse holder and diagnostic capability are
available for the power supply of other field potentials (DC 24 V, AC/DC 0 ...
230 V, AC 120 V, AC 230 V). The power supply modules can also be used to set
up various potential groups. The connections are connected in pairs to a power
contact.
Pos : 19.13.26 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Ans chl uss - Bild: F el dvers orgung (Standard + er weiterter ECO) @ 3\mod_1232950085156_21.doc x @ 26704 @ @ 1

Figure 7: Field supply for standard couplers/controllers and extended ECO couplers

Pos : 19.13.27 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Leg ende z u Abbildung "F el dvers orgung für Standard-F eldbus k/F el dvers orgung - Legende zu Abbil dung "F eldversorgung für Standard-Fel dbus k/-contr oller u er w EC O-F" @ 16\mod_1375693993330_21.doc x @ 127730 @ @ 1
Table 6: Caption for " Field supply (sensor/actuator) for standard couplers/controllers and extended
ECO couplers"
Field supply
1
24 V (-15 % / +20 %)
2
0 V
3
Optional ground potential
Power jumper contacts
4
Potential distribution to adjacent I/O modules
Pos : 19.13.28 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Ans chl uss - Weiterl eitung Vers orgungsspg., Strombel astung 10 A, neue Eins peisekl emme @ 8\mod_1279805441785_21.doc x @ 60845 @ @ 1
The supply voltage for the field side is automatically passed to the next module
via the power jumper contacts when assembling the I/O modules.
The current load of the power contacts must not exceed 10 A on a continual basis.
750-375 PROFINET IO advanced Fieldbus Coupler