System Description
Pos : 19.13.13 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Beis piel: @ 3\mod_1232630417843_21.doc x @ 26605 @ @ 1
Example:
Pos : 19.13.14 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Beispi el 1 (er weiterter ECO) @ 3\mod_1232950106250_21.doc x @ 26788 @ @ 1
Calculating the current consumption on an Example Coupler:
Internal current consumption
Residual current for bus modules
Sum I
(5 V) total
Pos : 19.13.15 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Inter ne Stromaufnahme/Summenstr om @ 3\mod_1232950111375_21.doc x @ 26816 @ @ 1
The internal current consumption is indicated in the technical data for each bus
terminal. In order to determine the total requirement, add together the values of all
I/O modules in the node.
Observe total current of I/O modules, re-feed the potential if required!
If the sum of the I/O modules' internal current consumption exceeds the residual
current for I/O modules, then an internal system supply module must be placed
before the module where the permissible residual current was exceeded.
Pos : 19.13.16 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Beis piel: @ 3\mod_1232630417843_21.doc x @ 26605 @ @ 1
Example:
Pos : 19.13.17 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Beispi el 2 (er weiterter ECO) @ 3\mod_1232950108359_21.doc x @ 26799 @ @ 1
Calculating the total current on the Example Coupler described above:
A node with the example coupler, which is described above, consists of:
20 relay modules (750-517) and 10 digital input modules (750-405).
Internal current consumption
Sum
The example coupler can provide 1620 mA (see previous example) for the bus
modules. This value is given in the associated data sheet. Consequently, an
internal system supply module (750-613), e. g. in the middle of the node, should
be added.
Pos : 19.13.18 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Berec hnung Ei ngangsstrom @ 3\mod_1232950109984_21.doc x @ 26808 @ @ 1
Recommendation
Utilize the smartDESIGNER feature WAGO ProServe
fieldbus node assembly. You can test the configuration via the integrated
plausibility check.
The maximum input current of the 24 V system supply is 500 mA. The exact
electrical consumption (I
750-375 PROFINET IO advanced Fieldbus Coupler
380 mA at 5 V
1620 mA at 5 V
2000 mA at 5V
20 * 90 mA = 1800 mA
10 * 2 mA =
) can be determined with the following formulas:
(V)
WAGO-I/O-SYSTEM 750
20 mA
1820 mA
®