Table 176: Parameterization AO – Attribute "Substitute value (2 Byte)"
Attribute Name
Substitute value
(2 Byte)
14.2.8
Analog Output Module with Diagnostics (AO, DIA)
If the analog output module provides diagnostic data, the following attributes can
also be set channel-by-channel during parameterization.
Table 177: Parameterization – Overview of additional Attributes for Analog Output Modules with
Diagnostics (AO, DIA)
Additional Attributes for Analog Output Modules with Diagnostics (AO, DIA)
-
Channel diagnosis (additionally)
-
Diagnosis: Short circuit (additionally)
-
Diagnosis: Undervoltage (additionally)
-
Diagnosis: Overtemperature (additionally)
-
Diagnosis: Error (additionally)
-
Diagnosis: External fault (additionally)
Table 178: Parameterization AO, DIA – Attribute "Channel diagnosis"
Attribute Name
Channel diagnosis
Table 179: Parameterization AO, DIA – Attribute "Diagnosis: Short circuit"
Attribute Name
Diagnosis: Short
circuit
Table 180: Parameterization AO, DIA – Attribute "Diagnosis: Undervoltage"
Attribute Name
Diagnosis:
Undervoltage
750-375 PROFINET IO advanced Fieldbus Coupler
Attribute Value
Description
In the state of missing output data, the set
-32767 ... 0
substitute value is output on the respective output
... 32767
channel with the set substitute value behavior
"Output substitute value".
Attribute Value
Description
If the analog output module provides diagnostic
0 (false)
data, the following attributes can also be set
channel-by-channel during parameterization.
If the analog output module provides diagnostic
1 (true)
data, the following attributes can also be set
channel-by-channel during parameterization.
Attribute Value
Description
A short circuit on the respective signal channel
does not lead to transmission of a diagnostic alarm
0 (false)
nor to entry in the diagnostics database of the
station proxy.
A short circuit on the respective signal channel
leads to transmission of a diagnostic alarm. The
1 (true)
respective error leads to an entry in the diagnostics
database of the station proxy.
Attribute Value
Description
A low voltage on the respective signal channel
does not lead to transmission of a diagnostic alarm
0 (false)
nor entry in the diagnostics database of the station
proxy.
A low voltage on the respective signal channel
leads to transmission of a diagnostic alarm. The
1 (true)
respective error leads to an entry in the diagnostics
database of the station proxy.
WAGO-I/O-SYSTEM 750
Manual
Version 1.1.0