Indirect Start Via Wago-I/O-Check From The Configuration Program (Device Level Tci Conformance Class 2); Indirect Start Via Wago-I/O-Check From The Configuration Program (Module Level Tci Conformance Class 2); Direct Start From The Configuration Program (Device Level Tci Conformance Class 3); Direct Start From The Configuration Program (Module Level Tci Conformance Class 3) - WAGO -I/O-SYSTEM 750 Manual

4fdi/4fdo 24v/2a profisafe v2 ipar, fail-safe 4/4 channel digital input/output, 24 vdc, 2 a, profisafe v2.0 ipar
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
8.3.3.3
Indirect Start via WAGO-I/O-CHECK from the Configuration Program
(Device Level TCI Conformance Class 2)
In the configuration program of the safe PLC, select a device (fieldbus coupler)
and launch "WAGO-I/O-CHECK 3" from the TCI link. The configuration program
passes the current language and communication setting to WAGO-I/O-CHECK.
Select an F I/O module for parameterization from the fieldbus node configuration
displayed in WAGO-I/O-CHECK. WAGO-I/O-CHECK then starts WAGO Safety
Editor 75x with the current language and communication settings. The Safety
Editor is started in ONLINE mode.
Communication occurs over the serial connection for a PROFIBUS fieldbus
coupler and over ETHERNET for a PROFINET fieldbus coupler.
If you want to exit the configuration of the F I/O module and to close the Safety
Editor, then WAGO-I/O-CHECK is also closed.
8.3.3.4
Indirect Start via WAGO-I/O-CHECK from the Configuration Program
(Module Level TCI Conformance Class 2)
In the configuration program, select an F I/O module and from the TCI link
"WAGO-I/O-CHECK 3", start the WAGO-I/O-CHECK. The configuration program
passes the current language and communication setting to WAGO-I/O-CHECK.
WAGO-I/O-CHECK then starts WAGO Safety Editor 75x with the current
language and communication settings. The Safety Editor is started in ONLINE
mode.
Communication occurs over the serial connecting cable for a PROFIBUS fieldbus
coupler and via the TCP/IP connection for a PROFINET fieldbus coupler.
If you want to exit the configuration of the F I/O module and to close the Safety
Editor, then WAGO-I/O-CHECK remains open.
8.3.3.5
Direct Start from the Configuration Program (Device Level TCI
Conformance Class 3)
This option is not supported. Since no F I/O module can be selected for
parameterization, the Safety Editor is automatically closed after selecting a
device (fieldbus coupler) in the configuration program of the safe PLC and
launching the Safety Editor via the TCI link "WAGO Safety-Editor 75x".
8.3.3.6
Direct Start from the Configuration Program (Module Level TCI
Conformance Class 3)
In the configuration program of the safe PLC, select an F I/O module and from
the TCI link "WAGO-Safety-Editor 75x", start the WAGO-Safety-Editor 75x. The
configuration program passes the current language and communication setting to
the Safety Editor. The Safety Editor is started in ONLINE mode.
Communication occurs over the PROFIBUS fieldbus for a PROFIBUS fieldbus
coupler.
Version 1.4.2, valid from HW/SW Version 01/02
Commissioning
91
Manual