Process Image

The F I/O module 750-667/000-003 occupies five data bytes in the input and
output process image in the higher-level secure PLC. The secure PROFIsafe
telegrams to send and receive are stored in input and output bytes 0 ... 4.
The process image received different data depending on whether the module is
operated in PROFIsafe V1 or PROFIsafe V2 mode.
5.1

PROFIsafe V1 Mode

Table 31: Process Image PROFIsafe V1 Mode

Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 0 ... byte 4

Table 32: PROFIsafe Inputs, V1 Mode

Bit 7
X
I1
I2
I3
I4
X

Table 33: PROFIsafe Outputs, V1 Mode

Bit 7
F_Ack
O1
O2
O3
O4
0
F_Ack
Input data
Inputs
Status byte
Serial No.
CRC16 high byte
CRC16 low byte
Secure process data (PROFIsafe telegram)
Bit 6
Bit 5
X
X
Signal state I1 – Digital input channel 1
Signal state I2 – Digital input channel 2
Signal state I3 – Digital input channel 3
Signal state I4 – Digital input channel 4
Reserved
Bit 6
Bit 5
0
0
Signal state O 1 – Digital output channel 1
Signal state O 2 – Digital output channel 2
Signal state O 3 – Digital output channel 3
Signal state O 4 – Digital output channel 4
Reserved
User acknowledgement for diagnosed failure (Failure Acknowledgement)
Byte 0
Outputs
Byte 1
Control byte
Byte 2
Serial No.
Byte 3
CRC16 high byte
Byte 4
CRC16 low byte
Bit 4
Bit 3
Bit 2
X
I4
Bit 4
Bit 3
Bit 2
0
O4
Version 1.4.2, valid from HW/SW Version 01/02
Process Image
Output data
Bit 1
Bit 0
I3
I2
I1
Bit 1
Bit 0
O3
O2
O1
Manual
55