WAGO -I/O-SYSTEM 750 Manual page 116

4fdi/4fdo 24v/2a profisafe v2 ipar, fail-safe 4/4 channel digital input/output, 24 vdc, 2 a, profisafe v2.0 ipar
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

116 Diagnostics
Table 44: Diagnostic Messages
Alarm
Over temperature
Invalid individual
parameters
Invalid Individual
Parameters from
the iPar Server
Invalid F_CRC1
Manual
Version 1.4.2, valid from HW/SW Version 01/02
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
Diagnostic
Module diagnostics
type
Coding
0x0205
LED
Group error (E) red
indication:
The permissible operating temperature of
the semiconductor in the F I/O module has
Remedy
been exceeded. Make sure that the
ambient temperature is within the specified
range.
Diagnostic
Module diagnostics
type
Coding
0x0200
LED
Group error (E) red,
indication:
parameterization (H) red, 1 Hz flashing
The individual parameter set for the F I/O
module is inconsistent. Correct the
Remedy
parameterization taking into account
dependencies between individual settings.
Diagnostic
Module diagnostics
type
Coding
0x004B
LED
Group error (E) red,
indication:
parameterization (H) red, 1 Hz flashing
The individual parameter set for the F I/O
module provided by the iPar server are
inconsistent. Make sure that a valid
Remedy
individual parameter set exists on the iPar
server. If necessary, check the fieldbus
transmission.
Diagnostic
Module diagnostics
type
Coding
0x0047
LED
Group error (E) red
indication:
PROFIsafe (G) red
The F_CRC1 form from the F parameter
Remedy
set is invalid. Create a consistent F
parameter set.
WAGO-I/O-SYSTEM 750
Description

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-667/000-003

Table of Contents