WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
8.3.4

Adjustable Parameters

Table 37: Adjustable Parameters

Parameter
Input filter time [ms]
Short circuit test I1
Short circuit test I2
Short circuit test I3
Short circuit test I4
Dual channel evaluation
I1 & I2
Dual channel evaluation
I3 & I4
Discrepancy time I1 & I2 [ms] 10 ... 100* ... 65535
Discrepancy time I3 & I4 [ms] 10 ... 100* ... 65535
Valence evaluation I1 & I2
Valence evaluation I3 & I4
Restart inhibit I1 & I2
Restart inhibit I3 & I4
Operating mode
Open load detection O1
Open load detection O2
Open load detection O3
Open load detection O4
Test pulse length O1 [ms]
Test pulse length O2 [ms]
Test pulse length O3 [ms]
Test pulse length O4 [ms]
* Standard setting
Value Range
0 (off) / 0.2 / 0.5 / 1 / 2 / 3* / 5 / 10 / 20 / 50 / 100 /
200
not active / active*
not active / active*
not active / active*
not active / active*
yes/no*
yes/no*
equivalent* / antivalent
equivalent* / antivalent
yes* / no
yes* / no
Standard* /
Rotary table, i.e. all safe inputs I1 ... I4 are
sensitive to T1
not active* / active
not active* / active
not active* / active
not active* / active
0 (off) / 1 / 2 / 5* / 10 / 20 / 50 / 100 / 200 / 500
0 (off) / 1 / 2 / 5* / 10 / 20 / 50 / 100 / 200 / 500
0 (off) / 1 / 2 / 5* / 10 / 20 / 50 / 100 / 200 / 500
0 (off) / 1 / 2 / 5* / 10 / 20 / 50 / 100 / 200 / 500
Version 1.4.2, valid from HW/SW Version 01/02
Commissioning
93
Manual