112 Diagnostics

Table 44: Diagnostic Messages

Alarm
Differing
F_Dest_Add
Discrepancy time
exceeded
Incorrect
F_CRC_Length
Incorrect
F_Par_Version
Manual
Version 1.4.2, valid from HW/SW Version 01/02
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
Diagnostic
Module diagnostics
type
Coding
0x0040
LED
Group error (E) red
indication:
PROFIsafe (G) red
The PROFIsafe address assigned as part
of the F parameterization differs from that
Remedy
set on the F I/O module.. Check the DIP
switch setting or PROFIsafe address set
using the safety editor (SEDI).
Diagnostic
Channel diagnostics
type
Coding
0x021E
LED
Status In (A, B, C or D) red,
indication:
group error (E) red
For 2-channel analysis of the input pair,
the F I/O module has determined that the
Remedy
discrepancy time set has been exceeded.
Check the connected contacts. Adjust the
discrepancy time setting if necessary.
Diagnostic
Module diagnostics
type
Coding
0x0045
LED
Group error (E) red
indication:
PROFIsafe (G) red
The configured F_CRC length is not
possible in the current operating mode.
Remedy
Observe the dependency between
F_Par_Version and F_CRC_Length and
select a valid combination.
Diagnostic
Module diagnostics
type
Coding
0x0046
LED
Group error (E) red
indication:
PROFIsafe (G) red
The set version of the F parameter set is
incorrect. Observe the dependency
Remedy
between F_Par_Version and
F_CRC_Length and select a valid
combination.