Another iParameter set description dialog opens. In this dialog, verify the
information given on the project, on the changes made, and on the personnel in
charge and change the information if need be. Click [OK] to confirm.
In the Input column of the parameter table of the Safety Editor, you can now
make the desired changes to the parameter values.
If you click on a parameter value with the left mouse button, depending on the
parameter you have selected, either a selection list of the possible settings for
this parameter appears or you can enter one of the possible parameter values
directly.
If all settings are correct, save the parameter set in a parameter file. To do so,
click [Save] in the Safety Editor toolbar.
The iParameter set description dialog opens for the detailed description of the
parameter file. In this dialog, enter information about the project, the changes
made, and the person responsible. Confirm your entries by clicking [OK].
Then the Save WAGO safety parameter set dialog opens. Enter a name for the
parameter file and select the directory in which the file is to be saved. Then click
on [Save] in order save the file to the hard disk.
To print the parameter values and information on the parameter file, click on the
[Print] button in the Safety Editor toolbar.
The Safety Editor provides additional services. Click the [Services] button on the
System Editor toolbar. A selection menu appears with the Compare menu item.
Comparison of parameter data!
With this function, only parameter data of the same I/O module type and
iParameter set format can be compared!
To compare two iParameter sets with each other, select the Compare menu
item. The Comparison of iParameter sets dialog opens.
To load a parameter file saved on the PC for comparison, click the [Open] button
and select whether the data set should appear in the "Reference" or
"Comparison" column".
To return the comparison dialog to its original state, click the [Delete] button.
To print the results of the comparison between to data sets, click the [Print]
button.
To exit the Safety Editor comparison dialog, click the [Close] button.
To close the Safety Editor, click on [Exit] in the Safety Editor toolbar.