Table 46: Description Of Marking Example For Approved Ex I I/O Module According To Atex And Iecex; Table 48: Description Of Marking Example For Approved Ex I I/O Module - WAGO -I/O-SYSTEM 750 Manual

4fdi/4fdo 24v/2a profisafe v2 ipar, fail-safe 4/4 channel digital input/output, 24 vdc, 2 a, profisafe v2.0 ipar
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

128 Use in Hazardous Environments
Table 46: Description of Marking Example for Approved Ex i I/O Module According to ATEX and
IECEx
Marking
TUEV 12 ATEX 106032 X
IECEx TUN 12 0039 X
Dust
II
3 (1) D
Ex
tc
[ia Da]
IIIC
T135°C
Dc
Mining
I
M2 (M1)
Ex
d
[ia Ma]
I
Mb
Gases
II
3 (1) G
Ex
ec
[ia Ga]
IIC
T4
Gc
Manual
Version 1.4.2, valid from HW/SW Version 01/02
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
Description
Approving authority resp. certificate numbers
Equipment group: All except mining
Category 3 (Zone 22) equipment containing a safety
device for a category 1 (Zone 20) equipment
Explosion protection mark
Type of protection: Protection by enclosure
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
circuits for use in Zone 20
Explosion group of dust
Max. surface temperature of the enclosure
(without a dust layer)
Equipment protection level (EPL)
Equipment Group: Mining
Category: High level of protection with electrical
circuits which present a very high level of protection
Explosion protection mark
Type of protection: Flameproof enclosure
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
electrical circuits
Explosion group for electrical equipment for mines
susceptible to firedamp
Equipment protection level (EPL)
Equipment group: All except mining
Category 3 (Zone 2) equipment containing a safety
device for a category 1 (Zone 0) equipment
Explosion protection mark
Equipment protection by increased safety "e"
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
circuits for use in Zone 0
Explosion group of gas and vapours
Temperature class: Max. surface temperature
135 °C
Equipment protection level (EPL)
WAGO-I/O-SYSTEM 750

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-667/000-003

Table of Contents