WAGO -I/O-SYSTEM 750 Manual page 113

4fdi/4fdo 24v/2a profisafe v2 ipar, fail-safe 4/4 channel digital input/output, 24 vdc, 2 a, profisafe v2.0 ipar
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
Table 44: Diagnostic Messages
Alarm
Error when
downloading the
individual
parameters
Error when
uploading the
individual
parameters
Internal error
Short Circuit
Diagnostic
Module diagnostics
type
Coding
0x004A
LED
No indicator
indication:
Timeout when writing (downloading) the
individual parameters from the iPar server.
Remedy
Check whether an iPar server instance
was created for the F I/O module and
whether an appropriate data set exists.
Diagnostic
Module diagnostics
type
Coding
0x0049
LED
No indicator
indication:
Timeout when saving (uploading) the
individual parameters to the iPar server.
Remedy
Check whether an iPar server instance
was created for the F I/O module.
Diagnostic
Module diagnostics
type
Coding
0x0209
LED
Group error (E) red
indication:
The internal hardware test of the F I/O
module failed or the operating program is
no longer running properly. Immediately
Remedy
replace the F I/O module and return it to
WAGO Kontakttechnik GmbH & Co. KG
for fault analysis.
Diagnostic
Channel diagnostics
type
Coding
0x0201
LED
Status In (A, B, C or D) red,
indication:
group error (E) red
The input of the F I/O module is not
supplied by the associated clock output or
Remedy
is connected to a +24V field supply
directly. Check the input wiring.
Version 1.4.2, valid from HW/SW Version 01/02
Diagnostics 113