86
Commissioning
Only operate F I/O modules with active password protection!
Without using the iPar functionality, F I/O modules may only be operated in
safety-related applications with active password protection.
F I/O modules may be operated in safety-related applications without active
password protection if the F I/O module is operated with iPar functionality (see
section "Commissioning" > ... > "F I/O Module with iPar Functionality without iPar
Server").
The 75x 2.x WAGO Safety Editor can be started with various call versions.
Depending on the call option, the Safety Editor is started in either ONLINE or
OFFLINE mode.
ONLINE mode is used to change the parameter data of an F I/O module directly.
OFFLINE mode is used to create or change parameter data in a parameter file in
an F I/O module.
8.3.1

ONLINE Mode

When opening the Safety Editor, the current parameter set of the F I/O module is
read from permanent memory and displayed in the Input column of the
parameter table in the Safety Editor.
To access existing parameter files, click on the [Open] button in the Safety Editor
toolbar.
In the Open WAGO safety parameter set dialog, enter a name for the
parameter file and select the directory from which the file is to be loaded. Then
click on the [Open] button to load the selected file from the specified location.
Another iParameter set description dialog opens. In this dialog, verify the
information given on the project, on the changes made, and on the personnel in
charge and change the information if need be. Click [OK] to confirm.
In the Input column of the parameter table, you can now make the desired
changes to the parameter values.
If you click on a parameter value with the left mouse button, depending on the
parameter you have selected, either a selection list of the possible settings for
this parameter will be displayed or you can enter the desired value directly.
Any parameter value changed is marked with a pen symbol, displayed in the first
column of the parameter table.
After changing the parameter values, transfer them into the I/O module. To do so,
click on [WRITE] in the Safety Editor toolbar.