Use of default individual parameter set
You can use the default individual parameter set of the F I/O module without
changing the individual parameter settings. Apply the value of the F_iPar_CRC
parameter specified in the section "Appendix" ... "Overview of PROFIsafe F
Parameters" by setting the F_iPar_CRC to this value in the hardware
configuration environment.
If the F_iPar_CRC has been set correctly, a match with the iPar_CRC is
permanently stored in the F I/O module.
Then compile the hardware configuration and safety program and check the
assignment of the PROFIsafe subscribers to the respective run-time group. Then
transfer the entire project to the safe PLC.
Note when replacing an I/O module (e.g., in case of maintenance), note that the
F I/O module cannot be automatically reparameterized.
Diagnostic message when there is a difference between the F_iPar_CRC
and iPar-CRC!
When there is a difference between the F_iPar_CRC and iPar-CRC, note that the
"Error when downloading individual parameters" diagnostic message first
appears after about 4.5 minutes. As a remedy, adjust the individual parameters
of the F I/O module using the WAGO parameterization tool.
Observe the required workflows listed in the respective manufacturer's
documentation and check and document all safety functions.