WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
Internal test pulse also when test pulse duration = 0 ms!
(applies to SW version 06)
Please note that the F I/O module up to software version 06 also performs an
internal test pulse expressed by briefly switching off all digital power outputs
when the test pulse duration is set to 0 ms. This is necessary to achieve the high
diagnostic coverage level and typically lies at well under 1 ms. You have to take
this into account when laying out your connected actuators and sensors.
Behavior of the F I/O module in the event of a failure
If an error is detected on a digital input or digital power output by the F I/O
module, the entire F I/O module is passivated by the process image of all digital
inputs being set to "0" and all digital power outputs being switched off. For
detailed information, read the section "Diagnostics".