WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
4.6.10.2
Typical Response Time of the Digital Inputs in an Error-free Case
Only use response times in the event of a failure for the safety response
time!
To prevent any personal injury or property damage, only use the values of the
safe response time for errors for defining the safety response time (see Section
"Safe Response Time of Digital Inputs in the Event of a Failure"). Under no
circumstances may you use the response times for the digital inputs during error-
free operation for the design!
The following table lists the typical response times for the digital inputs in error-
free operation.
Table 26: Safe Response Time of the Digital Inputs in the Error-Free Operation
Signal
change
Input
filter time
0 ms
0.5 ms
1 ms
2 ms
3 ms
5 ms
10 ms
20 ms
50 ms
100 ms
200 ms
Standard Operating Mode
Single-
Channel
Evaluation
Analysis
Equivalent
0 1
1 0
0 1
15 ms
15 ms
15 ms
17 ms
17 ms
17 ms 9.5 ms
19 ms
19 ms
19 ms
21 ms
21 ms
21 ms
25 ms
25 ms
25 ms
33 ms
33 ms
33 ms
53 ms
53 ms
53 ms
93 ms
93 ms
93 ms
211 ms 211 ms 211 ms 59 ms 211 ms 59 ms 211 ms 211 ms
411 ms 411 ms 411 ms 109 ms 411 ms 109 ms 411 ms 411 ms
808 ms 808 ms 808 ms 209 ms 808 ms 209 ms 808 ms 808 ms
Version 1.4.2, valid from HW/SW Version 01/02
Valence
Valence
Evaluation
Antivalent
1 0
0 1
9 ms
15 ms
17 ms 9.5 ms
10 ms
19 ms
11 ms
21 ms
12 ms
25 ms
13 ms
33 ms
19 ms
53 ms
29 ms
93 ms
Device Description
Rotary Table
Operating
Mode
1 0
0 1
1 0
9 ms
15 ms
15 ms
17 ms
17 ms
10 ms
19 ms
19 ms
11 ms
21 ms
21 ms
12 ms
25 ms
25 ms
13 ms
33 ms
33 ms
19 ms
53 ms
53 ms
29 ms
93 ms
93 ms
Manual