WAGO -I/O-SYSTEM 750 Manual page 117

4fdi/4fdo 24v/2a profisafe v2 ipar, fail-safe 4/4 channel digital input/output, 24 vdc, 2 a, profisafe v2.0 ipar
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
Table 44: Diagnostic Messages
Alarm
Invalid
F_Dest_Add
Invalid
F_Source_Add
Invalid F_WD_Time
Undervoltage
Diagnostic
Module diagnostics
type
Coding
0x0041
LED
Group error (E) red
indication:
The PROFIsafe address of the F I/O
Remedy
module must lie within the range of 1 to
65534. Correct the F parameterization.
Diagnostic
Module diagnostics
type
Coding
0x0042
LED
Group error (E) red
indication:
PROFIsafe (G) red
The PROFIsafe address of the F host
Remedy
must lie within the range of 1 to 65534.
Correct the F parameterization.
Diagnostic
Module diagnostics
type
Coding
0x0043
LED
Group error (E) red
indication:
PROFIsafe (G) red
The monitoring time for fail-safe data
Remedy
exchange must be set to a value greater
than 0 ms. Correct the F parameterization.
Diagnostic
Module diagnostics
type
Coding
0x0202
LED
Group error (E) red
indication:
The 24V field supply of the F I/O module is
Remedy
below the specified tolerance. Correct the
power supply responsible.
Version 1.4.2, valid from HW/SW Version 01/02