Using A Backup Capaciter In Case Of Interruptions In The Power Supply; Figure 24: Infeed For Profisafe I/O Modules 75X-66X With Backup - WAGO -I/O-SYSTEM 750 Manual

4fdi/4fdo 24v/2a profisafe v2 ipar, fail-safe 4/4 channel digital input/output, 24 vdc, 2 a, profisafe v2.0 ipar
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-667/000-003 4FDI/4FDO 24V/2A PROFIsafe V2 iPar
7.2.1
Using a Backup Capaciter in Case of Interruptions in the
Power Supply
Brief voltage dips in the field power supply below permissible values (e.g., when
switching capacitive loads) also leads to passivation of the PROFIsafe I/O
module. To prevent unintended passivations, low-impedance supply lines and
sufficient power supply units must be used. Alternatively in addition, a capacitor
can be used to support the field supply voltage for the digital inputs. To this
effect, you can use a backup capacitor module for the WAGO-I/O-SYSTEM 750
with a capacity of 10000 μF (item No. 288-824). The back-up capacitor module
(item No. 288 824) has a maximum current carrying capacity of 1 A and cannot
be used to support the 24V field supply voltage for digital power outputs with
higher power requirements.
Figure 24: Infeed for PROFIsafe I/O Modules 75x-66x with Backup Capacitor Module 288-824
Version 1.4.2, valid from HW/SW Version 01/02